Online Inquiry

* Note: Please be sure to fill in the information accurately and keep the communication unblocked, we will get in touch with you as soon as possible

Submit
DWT35-11 (DWT-I, DWT-II) type roof ventilator
+
  • DWT35-11 (DWT-I, DWT-II) type roof ventilator

Product Overview
Installed on roofs and walls. When the working medium temperature is 25℃, the relative humidity should not exceed 90%, and the dust content of the medium (including solids and impurities) should not exceed 100mg/m.3.
The fan mainly consists of an impeller, air duct, hood, motor, and other accessories. The impeller uses an axial flow fan, with a large air volume, and can also reverse airflow if needed. The hood and base are made of lightweight, high-strength, and corrosion-resistant fiberglass material, featuring an aesthetically pleasing design and resistance to wind and rain. The materials are divided into iron plate type and fiberglass type.
The main function of the roof ventilator is to provide indoor ventilation for buildings such as petroleum, chemical, light textile, metallurgy, and machinery factories, offices, laboratories, and warehouses. It can adapt to different structural forms and usage needs of buildings, and can be used for transporting corrosive gases, with performance parameters consistent with WT35-11 and WT4-72.

 

Main parameters of axial flow roof fan

Model Number
(no.)
Impeller Diameter
(mm)
Blade Angle
(deg)
Rotational Speed
(r/min)
Matching Motor
(kw-p)
Air Volume
(m/h)
Total Pressure
(Pa)
2.8 280 30 1450 0.09-4 1464 48
3.15 315 30 1450 0.12-4 2072 59
3.55 355 30 1450 0.12-4 2977 74
4 400 30 1450 0.25-4 4263 95
4.5 450 30 1450 0.37-4 6070 121
5 500 30 1450 0.55-4 8327 149
960 0.37-6 5566 64
5.6 560 30 1450 1.1-4 11682 186
960 0.37-6 7724 81
6.3 630 30 1450 1.5-4 16639 236
960 0.75-6 11016 104
7.1 710 25 1450 3.0-4 23815 300
960 0.75-6 15766 131
8 800 25 1450 5.5-4 31325 354
960 1.5-6 20735 155
9 900 25 960 3.0-6 29529 196
10 1000 25 960 4.0-6 40508 242
11.2 1120 25 960 7.5-6 56909 304

 

Main parameters of centrifugal roof fan

Model Number
(NO.)
Rotational Speed
(r/min)
Matching Motor
(kw-p)
Flow Rate
(m3/h)
Total Pressure
(Pa)
3.6 1450 1.1-4 1332-2634 393-247
4 1450 1.1-4 2006-3709 501-329
4.5 1450 1.1-4 2856-5281 634-416
5 1450 2.2-4 3864-7728 790-502
6 1450 4.0-4 6677-13353 1139-724
960 1.5-6 4420-8841 498-317
730 3.0-8 7968-14773 512-376

TAG:

DWT35-11 (DWT-I, DWT-II) type roof ventilator
+
  • DWT35-11 (DWT-I, DWT-II) type roof ventilator

DWT35-11 (DWT-I, DWT-II) type roof ventilator


Installed on the roof and walls. When the working medium temperature is 25℃, the relative humidity should not exceed 90%.

Share to:



Product inquiry

Filling in your phone and E-mail information will help us to get in touch with you in time and solve your problems as soon as possible.